Self-calculation of an individual heating system
Self-calculation of an individual heating system

The heating system of a private house consists of heating devices, piping and locking and regulating mechanisms, all of which serve to transport heat from the heat generator to the end points of space heating. It is important to understand that the reliability, durability and efficiency of an individual heating system depends on its correct calculation and installation, as well as on the quality of the materials used in this system and its competent operation.

Heating system calculation

Let us consider in detail a simplified version of the calculation of the water heating system, in which we will use standard and generally available components. The figure shows schematically an individual heating system of a private house based on a single-circuit boiler. First of all, we need to decide on its power, since it is the basis of all calculations in the future. Let's perform this procedure according to the scheme described below.

Self-calculation of an individual heating system
Self-calculation of an individual heating system

Total area of the room: S = 78.5; total volume: V = 220

We have a one-storey house with three rooms, an entrance hall, a corridor, a kitchen, a bathroom and a toilet. Knowing the area of each individual room and the height of the rooms, it is necessary to make elementary calculations in order to calculate the volume of the entire house:

  • room 1: 10 m 2 · 2.8 m = 28 m 3
  • room 2: 10 m 2 2.8 m = 28 m 3
  • room 3: 20 m 2 2.8 m = 56 m 3
  • entrance hall: 8 m 2 · 2.8 m = 22.4 m 3
  • corridor: 8 m 2 2.8 m = 22.4 m 3
  • kitchen: 15.5 m 2 2.8 m = 43.4 m 3
  • bathroom: 4 m 2 2.8 m = 11.2 m 3
  • toilet: 3 m 2 · 2.8 m = 8.4 m 3

Thus, we calculated the volume of all individual rooms, thanks to which we can now calculate the total volume of the house, it is equal to 220 cubic meters. Note that we also calculated the volume of the corridor, but in fact there is not a single heating device indicated there, what is it for? The fact is that the corridor will also be heated, but passively, due to heat circulation, so we need to add it to the general heating list in order for the calculation to be correct and give the desired result.

Single-circuit gas boiler
Single-circuit gas boiler

We will carry out the next stage of calculating the power of the boiler based on the required amount of energy per cubic meter. Each region has its own indicator - in our calculations we use 40 W per cubic meter, based on the recommendations for the regions of the European part of the CIS:

40 W 220 m 3 = 8800 W

The resulting figure must be raised to a factor of 1.2, which will give us 20% of the power reserve so that the boiler does not constantly work at full power. Thus, we understand that we need a boiler that is capable of generating 10.6 kW (standard single-circuit boilers are produced with a capacity of 12-14 kW).

Radiator calculation

In our case, we will use standard aluminum radiators with a height of 0.6 m. The power of each fin of such a radiator at a temperature of 70 ° C is 150 W. Next, we will calculate the power of each radiator and the number of conditional edges:

  • room 1: 28 m 3 40 W 1.2 = 1344 W. We round up to 1500 and get 10 conditional edges, but since we have two radiators, both under the windows, we will take one with 6 edges, the second with 4.
  • room 2: 28 m 3 40 W 1.2 = 1344 W. Round up to 1500 and we get one radiator with 10 ribs.
  • room 3: 56 m 3 40 W 1.2 = 2688 W We round up to 2700 and we get three radiators: 1st and 2nd with 5 ribs, 3rd (side) - 8 ribs.
  • hallway: 22.4 m 3 40 W 1.2 = 1075.2 W. Round up to 1200 and we get two radiators with 4 fins.
  • bathroom: 11.2 m 3 45 W 1.2 = 600 W. Here the temperature should be slightly higher, it turns out 1 radiator with 4 ribs.
  • toilet: 8.4 m 3 40 W 1.2 = 403.2 W. Round up to 450 and get three edges.
  • kitchen: 43.4 m 3 40 W 1.2 = 2083.2 W. Round up to 2100 and get two radiators with 7 edges.
Self-calculation of an individual heating system
Self-calculation of an individual heating system

As a result, we see that we need 12 radiators with a total capacity:

900 + 600 + 1500 + 750 + 750 + 1200 + 600 + 600 + 600 + 450 + 1050 + 1050 = 10.05 kW

Based on the latest calculations, it can be seen that our individual heating system will cope with the load assigned to it without any problems.

Pipe selection

A pipeline for an individual heating system is a medium for transporting heat energy (in particular, heated water). On the domestic market, pipes for the installation of systems are presented in three main types:

  • metal
  • copper
  • plastic
Installation of heating from copper pipes
Installation of heating from copper pipes

Metal pipes have a number of significant disadvantages. In addition to being heavy and requiring special installation equipment and experience, they are also susceptible to corrosion and can build up static electricity. A good option is copper pipes, they are able to withstand temperatures up to 200 degrees and a pressure of about 200 atmospheres. But copper pipes differ in the specifics of installation (special equipment, silver solder and extensive experience are required), in addition, their cost is very high. The most popular option is plastic pipes. And that's why:

  • they have an aluminum base, which is covered with plastic on both sides, due to which they have great strength;
  • they absolutely do not allow oxygen to pass through, which makes it possible to reduce the process of corrosion formation on the inner walls to zero;
  • thanks to the aluminum reinforcement, they have a very low coefficient of linear expansion;
  • plastic pipes are antistatic;
  • have low hydraulic resistance;
  • no special skills required for installation.
Plastic pipes
Plastic pipes

System installation

First of all, we need to install sectional radiators. They must be placed strictly under the windows, warm air from the radiator will prevent cold air from entering from the window. For the installation of sectional radiators, no special equipment is needed, only a perforator and a building level. It is necessary to strictly adhere to one rule: all radiators in the house must be mounted strictly at the same horizontal level, the general circulation of water in the system depends on this parameter. Also observe the vertical arrangement of the radiator fins.

Heating radiator installation
Heating radiator installation

After installing the radiators, you can start laying pipes. It is necessary to measure the total length of the pipes in advance, as well as count the number of various fittings (elbows, tees, plugs, etc.). To install plastic pipes, you need only three tools - a tape measure, pipe scissors and a soldering iron. Most of these pipes and fittings have laser perforation in the form of notches and guide lines, which makes it possible to carry out the installation on site correctly and evenly. When working with a soldering iron, you should adhere to only one rule - after you have melted and docked the ends of the products, in no case do not scroll them if it was not possible to solder exactly the first time, otherwise it may leak in this place. Better practice in advance on the pieces that go to waste.

Welding of polypropylene pipes
Welding of polypropylene pipes
Heating from polypropylene pipes
Heating from polypropylene pipes

Additional devices

According to statistics, a system with passive water circulation will function properly if the area of the room does not exceed 100–120 m 2. Otherwise, special pumps must be used. Of course, there are a number of boilers in which pumping systems are already built and they themselves circulate water through the pipes, if you do not have one, then you should purchase it separately.

Circulation pump in the heating system
Circulation pump in the heating system

On the domestic market, their choice is very large, moreover, they meet all the necessary requirements - they consume little electricity, are silent and small in size. Circulation pumps are mounted at the ends of the heating branches. This way the pump will last longer as it will not be directly exposed to hot water.

Heating systems in a private house: photo, advice from the master
Heating systems in a private house: photo, advice from the master

An example of a one-pipe heating system with forced circulation: 1 - boiler; 2 - security group; 3 - heating radiators; 4 - needle valve; 5 - expansion tank; 6 - drain; 7 - water supply; 8 - coarse water filter; 9 - circulation pump; 10 - ball valves

From all of the above, it becomes clear that two or three people can easily cope with the installation of such a system, this does not require special professional skills, the main thing is to be able to use elementary construction tools. In our article, we examined an individual heating system assembled using standard components, their price and general availability will allow almost everyone to mount a similar heating system at home.